Skip to content

Micro single channel input unit – MCIM

Micro single channel input unit - MCIM

Installation
1)Inputs monitored for open and short circuit fault conditions.
2)Suitable for monitoring normally open volt free contacts (flow switches etc).
3)Connections suitable for single strand fireproof cable up to 2.5mm2 .
4)Loop and input cable screen must be connected to interface earth terminals.
5)The end of line monitoring resistor, must always be fitted at the end of the input wiring, if the input is unused the end of line resistor must be fitted at the interface input terminals. Note: No addressing of the interface is required (see control panel operation for details)

The MCIM is a single input, soft addressed micro interface, incorporating integral short circuit isolators. It is extremely compact and therefore ideal for incorporation into other equipment.
The MCIM is fully compatible with the current range of Eaton intelligent addressable fire control panels. It is suitable for monitoring a set of normally open, volt free contacts such as sprinkler system flow switches, auxiliary panel fire/fault signals as well as non fire input signals such as flow valve open contacts, generator start up, fire door closed etc.

Product Information:
1)Soft addressed
2)Integral short circuit isolator
3)Single address
4)Suitable for monitoring:
5)Flow switches
6)Non fire inputs
7)Auxiliary panels
8)Up to 200 units per loop

Benefits
1)Quick and simple to install
2)No hard addressing required (Plug and play)
3)Compact size
4)Programmable by Eaton site installer software as technical input/non fire input